Description
MODEL SUPER MAX+ 10KVA 33/31, ±120V(240VDC) HIGH FREQUENCY ONLINE UPS | |
CAPACITY | 10KVA/ 10KW |
DC VOLTAGE | +120VDC (20 Battery System) |
PHASE | 3 PHASE IN ~ 3 PHASE OUT (Also Confirgurable as 3 phase in / 1 phase out) |
INPUT | |
NOMINAL VOLTAGE | 3×400 VAC (3Ph+N) |
ACCEPTABLE VOLTAGE RANGE | 190~250VAC (3-Phase) @ 50% Load 305~478VAC (3-Phase) @ 100% Load |
FREQUENCY RANGE | 46~54 Hz or 56~64 Hz |
POWER FACTOR | > 0.99 @ 100% Load |
TOTAL HARMONIC DISTORTION THD(!) | <4% @ 100% R-Load, <5% @ 100% RCD Load at 230 VAC <6% @ 50% R-Load, <12% @ 50% RCD Load at 230 VAC |
OUTPUT | |
NOMINAL VOLTAGE | 3×360* /380/400/415 VAC (3Ph+N) |
AC VOLTAGE REGULATION | + 1% (Battery Mode) |
FREQUENCY RANGE | Synchronized Range : 46~54Hz @50Hz System or 56/64 Hz @60Hz System Battery Mode : 50Hz + 0.1Hz or 60Hz + 0.1 Hz |
CURRENT CREST RATIO | 3:1 (Max) |
HARMONIC DISTORTION | <2% THD (Linear Load) ; <5% THD (Non-Linear Load) |
OVERLOAD CAPABILITY | AC MODE: (100%-110% : 60Min) (110%-125%:10Min) (125%~150%:1Min) >150% : Immediately BATTERY MODE:(100%-110%:60Min) (110%-125%:10Min) (125%~150%:1Min) >150%: Immediately |
TRANSFER TIME | |
AC MODE TO BATTERY MODE | ZERO |
INVERTER TO BYPASS | ZERO (when phase lock fails, <4ms interruption occurs from inverter to bypass) |
WAVEFORM (BATTERY MODE) | PURE SINE WAVE |
EFFICIENCY | AC MODE: 95.5% ECO MODE: 98.5% BATTERY MODE: 94.5% |
BATTERY | |
BATTERY TYPE | VRLA / LEAD-ACID Type |
NUMBERS OF BATTERY | 20 Nos. |
CHARGING CURRENT (MAX.) | 12A Maximum, Adjustable =1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A, Default setting=4A |
CHARGING VOLTAGE | +/-13.65*N (N=10) |
PHYSICAL | |
DIMENTIONS PRODUCT (LxWxH) | 630x250x750 (in mm) |
NET WEIGHT PRODUCT (Kgs) | 28 Kgs. |
FEATURE | |
LCD PANEL | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PROTECTION | Overload, Overtemperature,Utility abnormal, UPS fault, UPS warning, battery low,etc |
ALARM | Battery Mode: Sounding every 4 seconds Low Battery: Sounding every second Overload: Sounding twice every second Fault: Continuously sounding |
ENVIRONMENT | |
OPERATING HUMIDITY / TEMP. | 95% RH & Non-Condersing / 0.50°C/ Forced Air. |
NOISE LEVEL | Less Than 58dB @ 1 Meter |
Operation Altitude** | < 1000m** |
STANDARDS | |
SAFETY | EN 62040-1:2008/A1:2013;IEC 62040-1:2008/A1:2013;CE low voltage directive |
EMC | PEN 62040-2: 2006(C3)CE EMC directive |
MANAGEMENT | |
SMART RS-232 OR USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC |
OPTIONAL SNMP | Power management from SNMP manager and web browser |
Reviews