Description
MODEL |
MAX LiFE ONLINE UPS 5KVA/48V |
INPUT | |
CAPACITY | 5000VA/5000W |
VOLTAGE | 220/230/240 VAC |
VOLTAGE RANGE | 110-280 VAC@50%Load ; 176-280 VAC@100% Load |
PHASE | SINGLE PHASE WITH GROUND |
FREQUENCY RANGE | 46Hz – 54Hz or 56Hz – 64Hz |
POWER FACTOR | >0.98 @ NOMINAL VOLTAGE (100% LOAD) |
INPUT CURRENT HARMONIC DISTORTION THD(i) | >8% |
OUTPUT | |
OUTPUT NOMINAL VOLTAGE | 220/230/240 VAC |
AC VOLTAGE REGULATION | +1% (BATTERY MODE) |
FREQUENCY RANGE | Synchronized Range: 50Hz System: 47-53Hz / 60Hz System: 57-63Hz Battery Mode: 50Hz+0.1^ or 60 Hz+0.1% |
CURRENT CREST RATIO | 3:1 (Max) |
HARMONIC DISTORTION | < 3% THD (Linear Load) : < 5% THD (Non-Linear Load) |
AC/DC TRANSFER TIME | ZERO |
INVERTER to BYPASS TRANSFER TIME | 4ms (Typical) |
WAVE FORM | Pure Sine Wave on AC Input Power Mode & 54 VDC on Battery Mode |
ON FULL CHARGED BATTERY EFFICIENCY | LINE MODE : 95% / ECO MODE: 99.5% / BATTERY MODE: 92.0% |
BATTERY | |
BATTERY VOLTAGE | 48V |
BATTERY TYPE | Lithium-ion or Lead Acid Battery* |
FLOATING CHARGE VOLTAGE | 52 VDC (Configurable up to 58 VDC From LCD) |
OVERCHARGE PROTECTION | 60 VDC |
CHARGING CURRENT (MAX.) | 60 A (Configurable 10A / 20A / 30A / 40A / 50A / 60A From LCD) |
INDICATION | |
LCD PANEL | Load Leval, Battery Leval, AC Mode, Battery Mode, Bypass Mode and Fault Indicator Via LCD |
ALARM | |
BATTERY MODE : Sounding every 5sec | LOW BATTERY: Sounding every 2 Sec. OVERLOAD: sounding every Sec. FAULT: Continously |
PHYSICAL | |
DIMENTIONS PRODUCT (LxWxH) | 465x190x318 (in mm) |
NET WEIGHT PRODUCT (Kgs) | 15.5 Kgs. |
ENVIRONMENT | |
OPERATING HUMIDITY / TEMP. | 0-95% RH & Non-Condersing / 0.50°C |
STORAGE TEMPERATURE | -15°C to 60°C |
MANAGEMENT | |
COMMUNICATION INTERFACE | RS-232 and USB. SNMP Card / MODBUS Card (Optional) |
Reviews