Description
| MODEL SUPER MAX+ 60 KVA HIGH FREQUENCY ONLINE UPS | |
| CAPACITY | 60KVA/ 60KW |
| PHASE | 3 PHASE IN ~ 3 PHASE OUT |
| INPUT | |
| NOMINAL VOLTAGE | 3×400 VAC (3Ph+N) |
| ACCEPTABLE VOLTAGE RANGE | 190~520VAC (3 PHASE) @ 50% Load 305~478VAC (3 PHASE) @ 100% Load |
| FREQUENCY RANGE | 46~54 Hz or 56~64 Hz |
| POWER FACTOR | > 0.99 @ 100% Load |
| HARMONIC DISTORTION (THDi) | <4% at full Linear Load |
| OUTPUT | |
| OUTPUT VOLTAGE | 3×360**/380/400/415 VAC (3Ph-N) |
| AC VOLTAGE REGULATION BATTERY MODE | + 1% (Battery Mode) |
| FREQUENCY RANGE | 46~54Hz or 56/64 Hz (Synchronized Range) 50Hz + 0.1Hz or 60Hz + 0.1 Hz (Battery Mode) |
| CURRENT CREST RATIO | 3:1 (Max) |
| HARMONIC DISTORTION (THDv) AT OUTPUT | < 2% THD (Linear Load) : < 5% THD (Non-Linear Load) |
| OVERLOAD CAPABILITY | AC MODE: (100%-110% : 60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms BATTERY MODE:(100%-110%:60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms |
| TRANSFER TIME | |
| AC MODE TO BATTERY MODE | ZERO |
| INVERTER TO BYPASS | ZERO |
| WAVEFORM (BATTERY MODE) | PURE SINE WAVE |
| EFFICIENCY | AC MODE: 95.5% / ECO MODE: 98.5%, BATTERY MODE: 94.5% |
| BATTERY | |
| BATTERY TYPE | SMF (VRLA) / LEAD-ACID BATTERIES |
| NUMBERS OF BATTERY | Default: 32 Nos. – Adjustable: 40 Nos. (Note: Double Bank in Series of (16~29) + (16~20) Battery with Center-Tapped Confirguration) |
| CHARGING CURRENT (MAX.) | 2A~18A(Adjustable) |
| CHARGING VOLTAGE | +/- 13.65V*N (N=16~20) |
| ALARM | |
| BATTERY MODE | Sounding every 4 seconds |
| LOW BATTERY | Sounding every seconds |
| OVERLOAD | Sounding twice every seconds |
| FAULT | Continuously sounding |
| PHYSICAL | |
| DIMENTIONS PRODUCT (DxWxH) | 815 x 300 x 1000 (in mm) |
| NET WEIGHT PRODUCT (Kgs) | 74 Kgs. |
| WARRANTY | 1 Year Product Warranty |
| ENVIRONMENT | |
| OPERATING HUMIDITY / TEMP. | <95% & Non-Condersing / 0.40°C |
| NOISE LEVEL / INGRESS PROTECTION (IP RATING) | Less Than 70dB @ 1 Meter |
| LCD INDICATION PANEL(5-INCH TOUCH DISPLAY) | UPS status, Load percentages & amperes on each phase at output, Output VA & Wattage in each phase. Battery level(Charging ampere & discharging ampere), Input/Output voltage (Phase to Neutral & phase to phase information), Input Line Current per phase, Input VA/Wattage/PF per phase, Temprature information, Data Log events(max 500 events) and Fault conditions. |
| MANAGEMENT | |
| SMART RS-232 OR USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10 Linux & Mac |
| OPTIONAL SNMP | Power Management From SNMP Manager and Web Browser |









Reviews