HF SUPERMAX+ 100KVA, 3PH:3PH, ±240V(40-Battery System), DUAL INPUT, 7 INCH TOUCH PANEL LCD DISPLAY

KEY FEATURES

  • True double-conversion
  • DSP technolozy guarantees high performance
  • Output power factor 1
  • Active power factor correction in all phases at input
  • 50Hz/60Hz frequency converter mode
  • ECO mode operation for energy saving (ECO)
  • Emergency power off function (EPO)
  • Generator Compatible
  • SNMP+USB+RS-232 multiple communications
  • 3-stage extendable charging design for optimized battery performance
  • Adjustable battery numbers 32-40 battery
  • Parallel can be done with either individual battery bank on each UPS, or with Common Battery Bank
  • Waveform (Battery Mode) : Pure Sine Wave
WEIGHT 250kg
DIMENSIONS (L W H) 97.4x60x160

 

 

Enquiry

Description

 MODEL SUPER MAX+ 100 KVA HIGH FREQUENCY ONLINE UPS
 CAPACITY  100KVA/ 100KW 
 PHASE  3 PHASE IN ~ 3 PHASE OUT

 

 INPUT
 NOMINAL VOLTAGE  3×400 VAC (3Ph+N)
 ACCEPTABLE VOLTAGE RANGE  190~520VAC (3 PHASE) @ 50% Load
 305~478VAC (3 PHASE) @ 100% Load
 FREQUENCY RANGE  46~54 Hz or 56~64 Hz
 POWER FACTOR  > 0.99 @ 100% Load

 

 OUTPUT
 OUTPUT VOLTAGE  3×360**/380/400/415 VAC (3Ph-N)
 AC VOLTAGE REGULATION BATTERY MODE  + 1% (Battery Mode)
 FREQUENCY RANGE  46~54Hz or 56/64 Hz (Synchronized Range)
 50Hz + 0.1Hz or 60Hz + 0.1 Hz (Battery Mode) 
 CURRENT CREST RATIO  3:1 (Max)
 HARMONIC DISTORTION (THDv) AT OUTPUT  < 2% THD (Linear Load) : < 10% THD (Non-Linear Load)
 OVERLOAD CAPABILITY  AC MODE: (100%-110% : 60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms
 BATTERY MODE:(100%-110%:60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms
 PARALELL CAPACITY  Up to 4 units in parallel with Either Common battery bank or Separate battery bank

 

 TRANSFER TIME
 AC MODE TO BATTERY MODE  ZERO
 INVERTER TO BYPASS  ZERO
 WAVEFORM (BATTERY MODE)  PURE SINE WAVE
 EFFICIENCY  AC MODE: 95.5% / ECO MODE: 98.5%, BATTERY MODE: 94.5%

 

 BATTERY
 BATTERY TYPE  SMF (VRLA)/ LEAD ACID BATTERIES
 NUMBERS OF BATTERY  Default: 32 Nos. – Adjustable: 40 Nos.
 CHARGING CURRENT (MAX.)  2A~24A(Adjustable)
 CHARGING VOLTAGE  +/- 13.65V*N (N=16~20)

 

 ALARM
 BATTERY MODE  Sounding every 4 seconds
 LOW BATTERY  Sounding every seconds
 OVERLOAD  Sounding twice every seconds
 FAULT  Continuously Sounding

 

 PHYSICAL
 DIMENTIONS PRODUCT (DxWxH)  97.4 x 60 x 160 (in mm)
 NET WEIGHT PRODUCT (Kgs)  250 Kgs.
 WARRANTY  1 Year Product Warranty

 

 MANAGEMENT 
 SMART RS-232 OR USB   Supports Windows® 2000/2003/XP/Vista/2008/7/8/10 Linux & Mac
 OPTIONAL SNMP  Power Management From SNMP Manager and Web Browser

 

ENVIRONMENT
 OPERATING HUMIDITY / TEMP.  <95% & Non-Condersing / 0.40°C
 NOISE LEVEL / INGRESS PROTECTION (IP RATING)  Less Than 75dB @ 1 Meter / IP-20
 LCD INDICATION  UPS status, Load percentages & amperes on each phase at output, Output VA & Wattage in each phase. Battery level(Charging ampere & discharging ampere), Input/Output voltage (Phase to Neutral & phase to phase information), Input Line Current per phase, Input VA/Wattage/PF per phase, Temprature information, Data Log events(max 500 events) and Fault conditions.

 

 MANAGEMENT 
 SMART RS-232 OR USB   Supports Windows® 2000/2003/XP/Vista/2008/7/8/10 Linux & Mac
 OPTIONAL SNMP  Power Management From SNMP Manager and Web Browser

Reviews

There are no reviews yet.

Be the first to review “HF SUPERMAX+ 100KVA, 3PH:3PH, ±240V(40-Battery System), DUAL INPUT, 7 INCH TOUCH PANEL LCD DISPLAY”

Your email address will not be published. Required fields are marked *