ON LINE UPS 1KVA MAX+ ISO TRX

KEY FEATURE

  • True Double-Conversion.
  • Microprocessor Control Optimizes Reliability.
  • Input Power Factor Correction.
  • Wide Input Voltage Range (110V-300V).
  • 50/60 Hz Frequency Converter mode.
  • ECO Mode for energy saving.
  • Emergency Power off (EPO) Function.
  • Adjustable Charging Current via LCD Panel.
  • SNMP/USB/RS-232 Multiple Communication (SNMP is Optional).
  • 3-Stage Smart Battery Charger design to optimize battery performance.
  • Comprehensive display allows easy monitoring and access of UPS Status.
    Generator Compatible.
  • Built in Galvanic Isolation Transformer.
WEIGHT 15.3kg
DIMENSIONS (L W H) 19×42.1×31.8

 

 

Enquiry

Description

INPUT
MODEL  MAX+ 1KVA ISO TRX
RATED CAPACITY  1000 VA / 900 Watts
NOMINAL VOLTAGE  208/208/220/230/240 VAC
INPUT VOLTAGE RANGE   Low Line Transfer – 160VAC/ 140VAC/ 120VAC/ 110VAC + 3% Based on load percentage 100% -80% / 80%-70% / 70%-60% / 60%-0
 Low Line Comeback – 175VAC / 155VAC / 135VAC/ 125VAC + 3%
 High Line Transfer – 300VAC + 3%
 High Line Comback – 290VAC + 3%
FREQUENCY RANGE  40 ~ 70 Hz 
PHASE  Single Phase with Ground
POWER FACTOR  ≥ 0.99 @ full load
THDI  <5% @220~230VAC on Full Chargerd Battery | THDU <1.6% @ Input and full linear load condition

 

 OUTPUT
 OUTPUT VOLATGE RANGE  208 / 220 / 230 / 240 V AC
 FREQUENCY RANGE (Battery Mode)
 AC VOLTAGE RANGE (Battery Mode)
 50Hz + 0.1 Hz (60Hz + 0.1 Hz)
 +2%
 FREQUENCY RANGE (Synchroized Mains Mode)  50Hz System: 47 ~ 57 Hz (60Hz System:57~63Hz)
 THD (Non Linear Load)  ≤4%
 OVERLOAD  >110%, 30s turn to Bypass Mode
 >150% instant turn to Bypass
 CURRENT CREST FECTOR  3:1
 SHORT CIRCUIT PROTECTION  5 cycles turn Off Inverter, no transfer to Bypass, provide Alarm (AC Mode), 5 cycles turn Off Inverter, provide Alarm(Battery Mode), Input Fuse blown or Breaker action
 WAVEFORM  Pure Sinewave
 TRANSFER TIME  AC Mode to Battery Mode- ZERO
 Inverter to Bypass- <4 ms
 Eco to Battery-8ms (Typical), 10ms (max)
 EFFECIENCY  AC MODE- 78% @Full Charged Battery
 ECO MODE- 84% @Full Charged Battery
 BATTERY MODE- 75%

 

 BATTERY
 BATTERY TYPE  SMVFRLA/ LEAD-ACID
 BATTERY NUMBER  30 VDC (12V x 3Pcs)
 CHARGING CURRENT (Max. from AC Input)  1A/2A/4A/6A/8A (Selectable), default 8A
 CHARGING VOLTAGE  41.1 VDC + 1%

 

 FEATURE
 LCD PANEL  UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
 PROTECTION  Overload, Overtemperature,Utility abnormal, UPS fault, UPS warning, battery low,etc
 ALARM  Battery Mode: Sounding every 4 seconds
 Low Battery: Sounding every second
 Overload: Sounding twice every second
 Fault: Continuously sounding  

 

 PHYSICAL
 DIMENTION  421 x 190 x 318 mm
 NET WEIGHT (Kgs.)  15.3 Kgs
 OUTLET NUMBER & TYPE | INLET TYPE  3-PIN 6Amp India Type Socket, 4 pcs | IEC C14 10A Socket

 

 ENVIRONMENT
 OPERATING HUMIDITY / TEMP.  95% & Non-Condersing / 0.40°C
 NOISE LEVEL  Less Than 58dB @ 1 Meter with Fan speed Control
 DEGREE OF INGREES PROTECTION  IP-20

 

 MANAGEMENT 
 SMART RS-232 OR USB   Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
 OPTIONAL SNMP  Power management from SNMP manager and web browser

Reviews

There are no reviews yet.

Be the first to review “ON LINE UPS 1KVA MAX+ ISO TRX”

Your email address will not be published. Required fields are marked *