Description
|
MODEL |
i-MAXX TRANSFORMER BASED ONLINE UPS |
| CAPACITY | 15KVA / 12KW |
| DC VOLTAGE SYSTEM | DEFAULT: 360VDC, ADJUSTABLE:348~384VDC |
| PHASE | 3 PHASE IN – 1 PHASE OUT |
| INPUT | |
| NOMINAL VOLTAGE | 3x380v / 400VAC/415VAC(3Ph+N+G) |
| ACCEPTABLE VOLTAGE RANGE | 165VAC~280VAC(Ph-N)/285VAC-485VAC (Ph-Ph) |
| FREQUENCY RANGE | 40Hz/60Hz+10% |
| OUTPUT | |
| NOMINAL VOLTAGE | DEFAULT=230 +1%, 208VAC / 220VAC / 230VAC (Adjustble) |
| AC VOLTAGE REGULATION | +1% (BATTERY MODE) |
| FREQUENCY RANGE | Mains Mode (Syncronized Range) : 50Hz+1% , Battery Mode : 50Hz+0.1Hz |
| POWER FACTOR/CREST FACTOR | 0.8/3.1 |
| TOTAL HARMONIC DISTORTION | <2% (Linear Load), <5% (Non-Linear Load) |
| TRANSFER TIME | |
| AC to DC MODE | ZERO |
| INVERTRE to BYPASS MODE | ZERO |
| OVERLOAD CAPABILITY | 110% FOR 10Min, 150% FOR 60Sec & 160% FOR 200ms |
| WAVEFROM | |
| BATTERY MODE | PURE SINEWAVE |
| STATIC BYPASS | |
| OVERLOAD / SHORT-CIRCUIT CAPABILITY | 150% FOR 1 HOUR; 180% FOR 30Sec; >200% FOR 200ms |
| CONNECTION TYPE / INPUT VOLTAGE RANGE | HARDWIRE 3 WIRE (1Ph+N+G) / 220VAC |
| EFFICIENCY | |
| AC MODE EFFICIENCY | >88% |
| BATTERY MODE EFFICIENCY | 90% |
| BATTERY & CHARGER | |
| RECOMMEDED BATTERY TYPE | LEAD ACID / TUBULAR / SMF |
| BATTERY CHARGING AMP. | DEFAULT: 5A, MAXIMUM=CAPACITY(KW)x(1-%LOAD) / BATTERY VOLTAGE |
| No. OF BATTERIES | (DEFUALT: 30Nos), (Adjustable: 29,30,31 & 32 Numbers) |
| MANAGEMENT | |
| RS-232 / USB & OPTIONAL SNMP | Supports Windows® 2000/2003/XP/VISTA/2008/7/8, LINUX and MAC |
| DRY CONTACTS / SNMP (Optional) | 5 SIGNALS: AC FAILURE, LOW BATTERY, UPS ALARM, BYPASS AND UPS FAULT/POWER MANAGEMENT FROM SNMP MANAGER AND WEB BROWSER (Optional) |
| ENVIRONMENT | |
| OPERATING TEMP. / HUMIDITY / NOISE LEVAL | TEMP: 0~5*C / HUMIDITY: 0~90% (N On-Condensing) / LESS THAN 60 dBA@1Meter |
| PHYSICAL | |
| DIMENTIONS PRODUCT (LxWxH) | 656x405x817 (in mm) |
| NET WEIGHT PRODUCT (Kgs) | 120 Kgs. |





Reviews